SUSPENDED
CEILINGS
Based
on 1998 California Building Code Standard 25-2, which
applies to systems with an installed weight (including
fixtures) of less than 4 pounds per square foot.
Note:
The terms 'drop', 'T-bar', and 'suspended' are used
interchangeably with respect to ceilings.
The
Grid and Vertical Support
The
main runners shall be supported at 4 feet on center
with 12 gauge hanger wires hung vertically from the
supporting structure with fasteners sufficient to support
a 100-pound load. These hanger wires may not exceed
1 in 6 out of plumb. Three wraps are required at each
wire connection. Hanger wires or other approved supports
are required at the ends of each main runner and cross
runner along the perimeter of the room. Hanger wires
shall not be deflected by any duct, pipe, etc. Splices
and intersections of runners shall have a positive connection
with a minimum load capacity of 60 pounds. Perimeter
wall angles are considered aesthetic closures with no
structural value unless they are part of an approved
structural system.
Horizontal
Bracing and the Compression Strut
Horizontal
bracing shall be installed not to exceed 12 feet on
center in both directions and at not more than 6 feet
from perimeter walls. It shall consist of 4-12 gauge
wires secured to the main runner within 2 inches of
a cross runner, and splayed at 90 degrees from each
other at an angle not exceeding 45 degrees from the
plane of the ceiling. At the point of connection of
the horizontal bracing wires on the main runner, compression
struts shall be attached to the main runner, extended
vertically and be attached to the supporting structure
above.
Lighting
Fixtures
All
fixtures shall be positively attached to the grid. Hanger
wires shall be attached to the main runners within 3
inches of each corner of the fixture. Lighting fixtures
weighing less than 56 pounds shall also have two hanger
wires attached at the diagonal corners of the fixture.
Air handling diffusers and pendant lighting must have
dedicated hangers.
Above
Ceiling Wiring
The
wiring above a drop ceiling cannot be secured to the
ceiling hanger wires. For exceptions refer to the 1996
edition of the National Electrical Code, Section 300-11(a),
(1) and (2).

If
you need additional information, please call the Building
Division at (650) 991-8061.
ECDmc041902
|