ELECTRICAL
INSTALLATION OF RESIDENTIAL SERVICES
Ref. 2007 California Electric Code
SERVICE ENTRANCE
Minimum
Size of Residential Service and Feeder Conductors
[CEC 310.15(B)(6)]
| Copper
AWG |
Amps
|
| 4
|
100 |
| 2 |
125 |
| 2/0 |
200 |
Conductor
Types must be rated for wet locations. Conductors
exposed to sunlight must be listed/marked sunlight
resistant. [310.8] e.g.:
Type THWN conductors
See
Table 310.15(B)(6) for complete list of amperes and
conductor types.
CLEARANCES
FOR SERVICE DROPS [CEC
230.9 & 230.24]
-
3
ft. from openable windows, doors, porches, balconies,
ladders, stairs, fire escapes & similar locations.
-
8
ft. above any roof surface with a pitch of less
than 4 in 12.
-
3
ft. above any roof surface with a pitch greater
than 4 in 12.
-
18
when passing over the overhang (eave) portion of
the roof, regardless of the pitch, provided the
overhang does not exceed 4 ft. and the length of
the drop above the overhang does not exceed 6 ft.
-
10
ft. above grade at the service entrance, also at
lowest point of the drip loop, and above areas that
are accessible only to pedestrians.
-
12
ft. above residential property and driveways.
-
1
ft. from communications wires/cables at any point
in the span including the point of attachment to
the building. [800.10(A)(4)]
Service
Mast [230.28]
Only
service conductors shall be attached to the mast.
SERVICE
GROUNDING/BONDING
1.
An unspliced main bonding jumper shall be used
to connect the equipment grounding conductor(s) and
the service disconnect enclosure to the grounded conductor
(neutral) of the system within the enclosure. [250.28]
2.
Service equipment, enclosures and raceways must
be bonded. [250.92(A)] Bonding
shall apply at each end, and to all intervening raceways,
boxes, and enclosures, between the service equipment
and the grounding electrode.
The
following are acceptable bonding techniques: [250.92(B)]
Note:
Standard locknuts must be upgraded to the bonding type.
Grounding
Electrodes [250.52]
In
the City of Daly City, grounding electrodes for residential
service must be A, and
either B or C below:
A.
A metal underground water pipe in direct contact
with the earth for 10 ft. or more and electrically continuous
by bonding around insulating joints to the points of
connection of the grounding electrode conductor. Interior
metal water piping located more than 5 ft. from the
point of entrance to the building shall not be used
as a part of the grounding electrode system or as a
conductor to interconnect electrodes that are part of
the grounding electrode system.
B.
A
concrete encased electrode an electrode encased by
at least 2 of concrete, located within and near the
bottom of a concrete foundation or a footing that is
in direct contact with the earth, consisting of at least
20 ft. of one or more bare or zinc galvanized steel
reinforcing bars or rods (rebar) of not less than ½
inch in diameter, or of at least 20 ft. of bare copper
conductor not smaller than 4 AWG.
Rebars shall be permitted to be bonded together
by the usual steel tie wires or other effective means.
C.
A
ground rod, copper or copper clad plated steel, ½ to
5/8 in diameter and 8-10 ft. long, driven at least
8 ft. into the ground.
Note:
For other types of grounding electrodes and installation
procedures refer to NEC 250.52 & .53
Note:
Two different types of grounding electrodes are required;
for service upgrades this usually means the water pipe
and a ground rod.
The
Grounding Electrode Conductor (GEC)
Materials
(DCMC
15.24.070)
Installation
-
#8
AWG (min. size) requires physical protection [250.64(B)]
-
#6
AWG requires protection if subject to physical
damage
-
#4
requires protection if subject to severe physical
damage (e.g. along driveway).
Protection
is usually in the form of EMT, armor cable or rigid
conduit. All
of these methods must be properly bonded at both ends.
[250.64(E)]
GEC
Connection to Electrode
1.
The connection is to be accessible unless buried
or encased in concrete. [250.68 (A)]
2.
The connection is to be made with listed lugs,
clamps or other listed materials.
Note:
If buried, the lug or clamp must be listed for ground
contact. [250.70]
GEC
Connection at the Service
1.
The GEC shall be connected to the grounded service
conductor (neutral). [250.24(C)]
This
connection typically occurs at the neutral terminal
of the main disconnect enclosure.
Capacity
of GEC
(Table 250.66)
-
#8
AWG is rated for a #2 AWG size service entrance
conductor; #6 AWG up to size #1/0, and #4 AWG up
to#3/0.
-
The
GEC to a ground rod need not exceed #6 AWG in size
[250.66(A)]
-
The
GEC to a concrete encased electrode need not exceed
#4 AWG in size [250.66(B)]
Other
Bonding Requirements [250.104]
Bonding
of Piping Systems
(A)
Metal Water Piping systems installed in, or attached
to a building, shall be bonded to the service equipment
enclosure, the grounded conductor (neutral) at the service,
the GEC where of sufficient size, or to the one or more
grounding electrodes used. The bonding jumpers shall be sized in accordance with Table
250.66.
Other
Bonding Requirements [250.104]
(B)
Other Metal Piping, where installed in or attached
to a building, including gas piping, that may become
energized shall be bonded to the service equipment enclosure,
the grounded conductor (neutral) at the service, the
grounding electrode conductor where of sufficient size,
or to the one or more grounding electrodes used.
The
points of attachment of the bonding jumper(s) shall
be accessible.
Working
Space Required at the Service
[110.26 (A) (E)]
-
66
headroom
-
30
minimum width
-
36
minimum depth measured from the face of enclosure
-
Meter
height 48 66 (PG&E)
-
Illumination
shall be provided for working space at service equipment
installed indoors.
Daly
City Municipal Code Requirements
1.
(DCMC 15.24.030) Service entrance conductors
shall be enclosed in rigid metal conduit (RMC). Note:
PG&E requires a minimum of 1-1/4 diameter service
mast.
2.
(DCMC 15.24.070) Conductor material shall be
copper only.
3.
(DCMC 15.24.040) The meter and main disconnect must
be accessible from the exterior.
Note:
A lockable, gated entry compromises this access requirement.
4.
(DCMC 15.24.040) The service equipment must
be screened from public view by an enclosure.
Other
Items
Panel
Directory/Circuit Directory [408.4]
All circuits shall be legibly identified as to the purpose
or the use on a circuit directory located on the face
or inside of the panel door.
Grounded
Conductor
[200.6(A)(1-3)]
Color
- An
insulated grounded (neutral) conductor of 6 AWG and
smaller shall be identified by a continuous white outer
finish along its entire length [200.6(A)]. This
means you cannot
re-color a conductor to make it white for these sizes.
An
insulated grounded (neutral) conductor larger than 6
AWG can be re-colored in the field; this re-coloring
must occur at time of installation, by a distinctive
white or gray marking at its termination [200.6(b)(3)].
Terminations
Each
grounded (neutral) conductor shall terminate within
the panelboard in an individual terminal that is not
also used for another conductor [408.41]. I.e.
One conductor, one screw.
Circuit
Breakers & Size of Conductors [240.4(D)]
14
AWG size conductors are limited to 15 ampere rated breakers.
12
AWG size conductors are limited to 20 ampere rated breakers.
Service
Drop
[230.54]
Service
heads shall be located above the point of attachment
of the service conductors to the building.
Rating
of Cabinet/Service Equipment All cabinets installed
outdoors must be rated NEMA 3 (this includes cabinets
within enclosures designed to screen equipment from
public view).
Building
Division Telephone Number:
(650)
991-8061
ECDmc020209
|